The In-Between Voltage State
December 2005
By R. Austria, Pterra Consulting
Among steady-state techniques, one of the most common methods for
evaluating voltage stability is through the venerable P-V curve, also
known as the "knee" curve. This method is used to identify
the real power, or megawatt, margin to the point when the transmission
grid is no longer able to support voltages, a state the industry has
referred to as "voltage collapse." Many analysts have long
suspected that the P-V curve at best provided an approximate indicator,
and that there was a lot more it was not capturing. Recent
indications from near voltage collapse events seem to confirm that there
is indeed a lot more, which may perhaps require a re-thinking of the
whole process of using steady-state methods for voltage analysis.
Flexing the Knee
In the traditional P-V curve analysis, the power
across a set of transmission paths is gradually increased by either
increasing load or reducing generation at the receiving end.
This would simulate, for example, the gradual rise in demand over time,
such as the weekday load rise, or the adjustments to increase
imports into a region. Several nodes or substations are selected where
voltage is monitored as a series of power flow solutions is performed.
The result is the P-V curve with its characteristic "knee" shape.
The power flow solution assumes at least one
critical factor that gives analysts concern --- generators are modeled
by static reactive limits. For periods of a second to several minutes,
generators are capable of delivering reactive power of up to 2 to
3 times the static limits, so-called transient vars [1]. What really happens in the short
timeframes? Is the effect sufficient to alter the P-V curve?
The answer to the second question is apparently
"yes." But surprisingly, the basis goes beyond just the transient reactive
capability of generators.
Generators deliver extra vars at the expense of
thermal heating. Oversized generators such as steam turbines in coal
and nuclear plants are able to deliver more transient vars since they
are able to tolerate more heating than smaller units such as gas
turbines. However, in a timeframe of minutes, rotor temperature control
requires the reduction of transient vars through either overexcitation
limiter protection or operator action. When generators reduce var
output, voltages drop. At this point, the action shifts away from
the observation of transmission network operators over to the
distribution system!
Tap-changing transformers serving distribution
circuits mask dropping voltages in the transmission network by
maintaining setpoint voltages at customer loads. The tap-changers will
do this until they exhaust the available tap steps, at which point
customer loads are exposed to a rapidly deteriorating voltage.
Capacitors do not help during this time as they themselves are losing
reactive output at the rate of square of the drop in voltage. In
addition, the following effects seek to push voltages further downwards:
-
Loads that have
low voltage tolerance that
allow them to recover to their normal demand level at lower terminal
voltages, such as variable speed motors, or thermostat-controlled
loads
-
Motor loads that
stall, causing an
increase in reactive demand
However, there are other
effects that help curb the deterioration of voltage:
-
The natural response of loads to decrease power
demand as terminal voltages decrease
-
The dropout of contactors due to low
voltage, most notably in motors, such as air conditioners and pumps
The combined effects of the above, as seen from the
transmission system, produce a
quasi-equilibrium characterized by voltages holding steady at the transmission
level, somewhere in the .9 to 1.0 per unit range, while distribution
voltages experience widely fluctuating and damaging voltages. This
condition may remain in place over an extended range of transfers and load levels, and thus
prevail over several hours. The net effect is a sort of voltage
"ledge" in the P-V curve where transmission voltages appear to be "normal."
One could liken this to the Brownian movement that occurs in the
molecules of a liquid that from all outward appearances is sitting
still.
Case Study
In July 1999, a situation characterized as a "near voltage
collapse event" provides a good, practical example of the voltage
ledge.
On this particular summer day, extremely high temperatures were
projected along the Eastern US seaboard. By noon, emergency
dispatch conditions and a 5% voltage reduction (where the distribution
voltage setpoints are reduced by 5%) had been called for. At about
1 PM, voltages at the 500 kV network had dropped to 1.0 per unit, an
unusual event, perhaps the first time ever, and yet not outside
acceptable operating limits. This condition remained for about 3
hours until load outages and cooling outside temperatures allowed
voltages to
recover. During 3 hours on the voltage ledge, over a thousand
pole-top distribution transformers failed, numerous motors stalled and
re-started, some repeatedly, primarily air conditioners, and reports of
damaged computers and TV sets and other sensitive equipment clogged call
centers. Distribution connected gas turbines failed to startup
because of low terminal voltage conditions.
In the aftermath of this event, root cause analysis indicated
the need for certain critical measures including more accurate modeling
of generator reactive capability, the need for static var devices,
must-run generators and possibly
undervoltage load shedding and a
broader study of the conditions that led to the disturbance.
Additional Comments
There is no doubt that the transient effects have an impact on the
P-V curve. Most of the time, the steady-state results are more
conservative in terms of providing margin to voltage instability.
However, it is significant to note that the voltage ledge starts around
1.0 per unit voltage, above where most P-V curves would consider voltage
collapse.
Clearly, dynamic simulation techniques provide a clearer view
of grid response during the transient period. Models for
self-restoring loads, overexcitation limiters, motor stall and re-start
and tap-changing transformers extend the reach of simulations beyond a
few seconds to the minutes timeframe that is needed to see how systems
behave in the voltage ledge.
References
The following references provide additional information on the
concepts and events described in this article.
- A. Murdoch, G.E. Boukarim, B.E. Gott, M.J. D’Antonio and R.A.
Lawson, “Generator
Overexcitation Capability,” Panel Session Summary for the IEEE/PES
2001 WPM, Columbus, OH, jointly sponsored by the Excitation System
Subcommittee and the
Power System Stability Controls Subcommittee.
-
Ricardo
Austria, et al, “Voltage Stability Assessment of the
National Grid System Using Modern Analytical Tools,” presented at
the 2001 Transmission and Distribution Conference and Exposition,
October 28 – November 2, 2001, Atlanta, George, USA.
- Robert T. Eynon, Thomas J. Leckey, and Douglas R. Hale, "The
Electric Transmission Network: A Multi-Region Analysis," EIA,
DOE.
- "Report
of the U.S. Department of Energy’s Power Outage Study Team, Findings
and Recommendations to Enhance Reliability from the Summer of 1999,"
Washington, DC, March 2000.
For questions, comments and further discussion, contact us at
mailto:info@pterra.us
© 2005. All rights reserved.
|
 
|