The Increasing Harmonic Penetration in Transmission Systems
March 2008
Printer-Friendly
Version
E. Cano and K. Dartawan,
Pterra Consulting
When the physicians of the power system
(planners and operators) treat for resource inadequacy, congestion,
instability and all the modern-day maladies of competitive power
markets, their regimen may come with an increasingly common side effect
– harmonics. The utilization of static var compensators (SVC),
induction generators, source converters, underground and submarine
cables, direct current converters, to name a few, to provide solutions
to power system problems can lead to increasing harmonic penetration in
the power system. Harmonic generating equipment coupled with system
resonance conditions effects are cumulative and can be
detrimental to system operations if not mitigated.
Sources of Increasing Harmonic Penetration
The following are the usual suspects for
escalating harmonic penetration in transmission systems:
-
Reactive Power Compensation. To address local voltage
problems, utilities use capacitor banks. Capacitors in transmission
systems are usually switched in blocks that may result in harmonic
resonance. The switching events can be cyclical over the course of
daily operation or in response to various system contingencies.
-
Wind Turbine Generator Speed Controls. Variable speed
controls of wind turbine generators employ power converters that
produce harmonics at the point of common coupling (PCC).
-
Wind Plant Power Factor Compensation and Low Voltage Ride Through
Capability. Wind turbines use induction generators that require
some form of power factor compensation to maintain unity power
factor at the low voltage PCC. The compensation may take the form
of capacitor banks. Wind turbine generators are further required to
have ride-through capability for low voltage conditions associated
with system faults and disturbances similar to synchronous
machines. Dynamic compensation to attain acceptable voltage
response during system disturbance may be specified. The dynamic
compensation can take the form of Static Var Compensator (SVC),
Static Compensator (STATCOM) and other forms of static var device
made up of high power electronics. Such devices produce harmonics
as a consequence of their operation.
-
Flexible Alternating Current Transmission System (FACTS) devices.
These devices are mostly considered for flexible control of the
transmission systems. Power flow control and reactive power control
are usually the application of FACTS. Sometimes, these devices are
useful for postponing transmission line investments or replacing
retired generation. Utilizing power electronic components, these
devices, even equipped with filters, can result in harmonic
resonance in combination with the system impedance.
-
High Voltage Direct Current (HVDC) Installations. Though
provided with harmonic filters to smooth the AC output, HVDC can
resonate with the system at various operating conditions thus
increasing harmonic content of transmission bus voltages and line
currents.
-
Underground and Submarine Cable Installations. To solve the
problems of right-of-way and environmental constraints, utilities
may consider underground or submarine transmission cables which have
high charging characteristics that can be comparable to reactive
power compensation.
The Scenario
The transmission system is a continuously
changing large scale system that is exposed to different generation
dispatches, load levels and line status conditions at various times
during the day, month or year. For one, the system is exposed to
multiple generation dispatches influencing interface flows and
line loadings. Each change in generation dispatch results in a different
short circuit profile. The consequent variation in apparent
impedances interacts in unique ways with harmonic sources in the
transmission system. This is further impacted by changes in the system
configuration such as may be due to outages, operational procedures and
maintenance. In addition, changes in load level and composition
present diverse modes for the damping of harmonics.
The changes in harmonic supply and damping may
result in more or less harmonics penetrating the grid at various times.
Furthermore, the risk of reaching resonant conditions is a
critical concern for operators and consumers alike.
Scanning Harmonics
The level of harmonic penetration is determined by
harmonic measurements (hardware) and harmonic simulations
(software). Measurements account for whether or not recommended
standard harmonic limits are met over a certain period of monitoring.
Evaluation of harmonic measurements, as a minimum,
are made against existing recommended or regulatory harmonic limits
utilizing industry accepted indices. The monitoring period needs
to capture all the various operating scenarios for proper analysis of
the increased harmonic content window. Harmonic simulations accounting
for proper modeling and harmonic power flow utilize electro-magnetic
transient software. Power flow transmission models can be easily
converted to such platform nowadays. Another option is programming
typical steady-state power flow software to compute for frequency
response. Such software solutions compute a so-called “frequency
scan”. Frequency scan analysis is initially conducted to achieve
perspective on the system response to additions of components to the
system and/or to different system operating scenarios. In figure 1,
a frequency scan of one transmission system bus with respect to several
operating conditions results in resonance to 3rd (black) and 5th
(green) harmonic frequencies. To further dig deeper into the
resonant situation, harmonic indices such as total harmonic distortion
and individual harmonic distortion should be conducted. If harmonic
distortion magnitudes surpass accepted industry limits, various harmonic
mitigation solutions are investigated.

Figure 1: Harmonic Frequency Scan
at a Transmission System Bus at various contingencies.
High power electronic devices used for power
system control generates harmonics that when coupled with harmonic
resonance can produce unacceptable harmonic quantities that may impact
equipment loading, nuisance protection tripping and unnecessary added
heating in system components.
Solutions
Knowing the potential and actual levels of
harmonic penetration gives transmission operators and planners the
opportunity to apply mitigation measures. Typical planning
mitigation may involve the installation of harmonic filters at strategic
locations.
Other solutions may include re-tuning of
controls of power electronic converters, reconfiguration of existing
harmonic filters and investigation of cable parameter sensitivity to
harmonic resonance. The latter may result in choosing a cable with
different characteristics, for instance.
Conclusion
Harmonic penetration in the transmission system
increases as the system is more heavily utilized and transmission and
generation additions result in conditions of resonance with existing
components at certain system operating states. The level of harmonic
dispersion is determined by conducting harmonic measurements and
simulations. Knowing the potential levels of harmonic penetration
allows for opportunities to mitigate through operating procedures
or planning solutions such as implementing filters.
Reference:
D. Mueller, “Case Studies of Harmonic Problems,
Analysis and Solutions on Transmission Systems”, 9th International
Conference on Electrical Power Quality and Utilization, Barcelona,
Spain, October 9-11, 2007.
© 2008. All rights reserved.
|