Rising Out of the Trench: Insight from the Voltage Response Curve
October 2007
Pterra Consulting
The Voltage Response Curve (or for purposes of this article,
the "VRC") is what you get when you plot the voltage at or near a system
node just before, during and immediately after an event involving a
fault and subsequent clearing. The VRC is a record of the dynamic
response of the system. It can be obtained from computer simulation, a well-isolated system test or a
disturbance recorder. In much the same way that planning and
operations personnel look at swing curves (Note 1) to determine if a
synchronous system is angularly stable, much can be deduced about the
underlying system and its voltage stability by studying the VRC.
A
sample VRC is shown at right. Before the fault occurs, the voltage
is at nominal, or 1.0 per unit (pu). When the fault occurs,
voltage drops and remains depressed while the fault is on. After a
few cycles, the fault is cleared by circuit breakers, which may
result in loss of a line or other system element. Immediately after the fault is
cleared the voltage recovers. Seconds later, the voltage
would settle at the post-transient value.
The shape of the VRC is that of a trench (note 2), where there is
an initial deep drop in voltage, followed by a short duration at very
low voltage, then a recovery period. The shape of the curve,
especially for the time period after the fault is cleared, says a lot about the
underlying grid's reactive power supply, including how close the
system is to voltage collapse. Hence, the VRC provides a measure
of voltage stability.
Furthermore, the VRC is a system characteristic whose shape is
consistent over a certain area of the grid, such as a load pocket,
regardless of location of the fault within that area. Hence, it
may be possible to identify the system based solely on the shape of the VRC. This
system characteristic allows operators and planners to set voltage
performance criteria that are specific to a system.
And yet, the same criteria that may work so well in one system may not apply
to another whose VRC characteristics may be different.
One Digression ...
Before taking a closer look at the shape of the VRC trench, let us
note, for example, the initial effort of FERC to specify the low voltage
ride through of wind farms. The proposed criteria is shown in the
Figure below (Note 3).

The concept behind this proposed criteria was that in providing wind
farms with the low-voltage ride-through capability, the wind farms will
be able to withstand the system VRC. However, there are a wide
variety of VRC shapes existing in US power systems. (The
criteria has been replaced.)
Continuing ...
Voltage Stability refers to the ability of a power system to restore
and maintain voltage at all buses in the system following a disturbance
from a given initial operating state. Voltage instability can occur in
heavily loaded systems when reactive power available from power system
equipment such as capacitors, transmission lines, generators, and static
var devices are less than the demand from loads and the requirement to
supply reactive losses.
Voltage
stability during the transient period is determined based on the shape
of the VRC in the first few seconds following a disturbance. For
instance, see the three VRCs shown at right. Each of the VRCs is
based on a different system configuration and dispatch, load model and
contingency. But we can make some general observations about those
systems by considering the shape of the VRC.
Typology
The Type 1 VRC (shown as the green
curve) has an overshoot after the fault is cleared. The voltage
rise indicates that there is available reactive power in the vicinity of
the fault, even after the loss of a line or transformer. This
reactive power may come from generators in the local area, and/or
generators remote to the area but connected to the area via transmission lines. This may also come about from fast
load shedding occurring during or immediately after the fault is
cleared. The "ringing" at the top of the response curve may come
from voltage regulators taking control of field voltage.
The Type 2 VRC (shown as the red curve)
has no overshoot and settles to the post-transient voltage immediately
after the fault is cleared. The underlying system may not have much
available reactive power following the fault. The voltage response
is defined primarily by the load characteristic. With more
constant impedance or constant current type loads, the post-fault return
to voltage will be even sharper than that shown.
The Type 3 VRC (shown as the blue curve)
settles at a very low voltage. In this case, the underlying system
does not have access to reactive power to recover the voltage within
acceptable limits. The system probably enters into a Voltage
Ledge, where, to compensate for the lack of reactive power, motors are
stalling, dropping out or restarting, and ZIP-type loads (Note 4) are at
a reduced level.
Conclusions
As we get used to checking for voltage stability through VRC curves,
we develop better insight on the underlying systems that produce such
curves. Such insight leads to better understanding of the nature
of any potential voltage instability, and the possible countermeasures
that would be effective for each situation.
Notes
- Swing curves - plots of rotor
angles of rotating equipment interconnected synchronously.
During a contingency, the rotor angles separate and whether the the
angles recover and re-synchronize or not determines the angular
stability of the system to the disturbance. The swing curves
are the characteristic response of the rotors whose angles appear to
swinging against and with each other.
- Oceanic trenches are narrow
topographic depressions of the sea floor. They are also the deepest
parts of the ocean floor.
- Voltage Response nomogram as proposed by the US FERC for wind
farm low-voltage ride through characteristics (United States Federal
Energy Regulatory Commission, order No. 661, Appendix B, June 2,
2005). This has since been replaced.
- ZIP loads - These are loads that respond in a specific voltage
characteristic. Constant Z (impedance) loads vary as the
square of voltage. This type of load includes most lighting, most
small motors loads. Constant I (current) loads vary in direct
proportion to voltage. This is an approximation of general response
from composite loads such as commercial areas and residential load.
Constant P (power) loads are invariant to voltage. These include
adjustable speed drive motors, computers, electronic equipment and
other loads.
© 2007. All rights reserved.
|