Observability and Controllability in Highly Compensated Systems
September 2007
Pterra Consulting
Shunt compensation, in the form of capacitor banks and
static var devices (SVD), are commonly used to provide voltage
support in heavily loaded systems. Shunt devices offer a
relatively cheap and easy-to-implement solution to
providing reactive power to load pockets or remote load areas
of the grid. In concept, one can add a combination of switched and
controlled shunt compensation to increase import capacity up to
the thermal limit of the transmission system. The savings
from deferred investment in new transmission or congestion costs
can justify the implementation of large shunt devices. (The largest existing SVDs
are a
+500/-150 MVAR behemoth in the Allegheny Power service territory in
Pennsylvania, USA, and the Chamouchouane SVC (actually two SVCs at one
site) rated +330/-330 MVAR in Quebec, Canada.)
But, the impact ...
The impact of static shunt devices on system operations can be
a concern. One such impact is a high operating voltage that
may show only a small dip before the demand reaches a voltage collapse
condition. This effect can be viewed from the perspective of the
P-V curve. The P-V curve is a plot of voltage at a
monitored bus as load or transfer is increased. A typical curve is
shown below. The curve has a "knee" shape and voltage
collapse eventually occurs at a level of load or transfer referred to as
the MW or voltage collapse limit.

When shunt compensation is added to the system, the shape of the
P-V curve changes, flattening the portion at lower load or transfer
levels and extending the P-V curve such as to obtain a higher MW
voltage collapse limit. Shunt compensation also raises the
voltage such that voltage collapse may occur at near or above
normal operational levels. (See figure at right.)
Hence, shunt compensation reduces observability by masking the
onset of voltage collapse from the normally monitored parameter of
system voltage.
Definitions
Observability is the aspect of the power
system that provides operators with indicators to
anticipate potential problems, in this case, voltage instability. The
indicators need to be of a form that operators can observe and monitor
in order to have sufficient time to respond to a system
disturbance. For voltage stability, the traditional observed quantities
are voltages at various nodes of the power system. However, when
operating a system with high compensation levels, the pre-contingency
voltage can be high, and voltage may not be a sufficient monitored
parameter to observe the voltage stability of the grid.
Controllability
is the aspect of the power system that provides operators with
sufficient control and response capability to maintain
reliability, or in this specific case, voltage stability. The
controls available to the operators of today include dispatch,
voltage schedules and switching of capacitors and lines, and load
adjustments. At high levels of shunt compensation, the sensitivity
of voltage to the controls is quite high, i.e., small shifts in dispatch
and voltage schedules may result in significant shifts in the voltage
stability of the system. The primary causes of this sensitivity
are shunt compensation devices in SVCs and capacitor banks whose
reactive output vary as the square of the terminal voltage. As voltage
shifts take place, the total reactive output from the static
devices changes, and needs to be balanced by the reactive output from
rotating devices.
Solutions
To enhance observability, additional monitored
parameters are required. One of the most commonly used indicators is the
reactive reserve. This is a measure of the level of reactive
output of generators and static devices. Although this measure is
typically determined from Q-V curves, dynamic simulation offers a
better alternative in identifying optimal levels of
reactive output from various reactive sources. Other indicators that
have been used in Europe and the United States include
- the rate of voltage change per MW change in load,
- the rate of reactive output change per MW change in load, and
- online dynamic security assessment tools.
To
improve controllability, additional supervisory and
supplementary controls may be specified. these my take the
form of wide-area monitoring or control, or a centralized reactive power
controller.
Conclusion
The result of high levels of shunt compensation added to a power
system is a loss of observability
and controllability. But there is a certain economic incentive
in adding shunt compensation in place of other alternatives, including
constructing new transmission. In concept,
switched and controlled shunt devices can be added to increase
transmission capacity up to the exiting thermal limit. Hence, some
very large SVCs, in the rating size above 500 MVA, have been
implemented, are under construction or are in the planning stages.
To compensate
for loss of observability through the classical means of monitoring
system voltages, operators need additional observed parameters and/or an
online
security assessment tool. To address the increase in
difficulty of
controlling the power system through the classical methods such as
switching and adjusting voltage setpoint, operators need further supplementary controls
such wide-area monitoring and control to be able to continue to maintain a reliable, voltage-stable system.
References
- Pterra Consulting, "South
Island Grid Upgrade Project Dynamic Voltage Stability Study Final
Report,", September, 2007.
- A Berizzi, S. Corse, D. Dosi, P. Finazzi, P. Marannino, and S.
Corsi, “First and second order methods for voltage collapse
assessment and security enhancement,” IEEE Trans. Power Syst., vol.
13, pp. 543–551, May 1998.
- C. Canizares, F. Alvarado, C. L. DeMarco, I. Dobson, and W. F.
Long, “Point of collapse and continuation methods for large ac/dc
systems,” IEEE Trans. Power Syst., vol. 8, pp. 1–8, Feb. 1993.
- Zima, M.; Larsson, M.; Korba, P.; Rehtanz, C.; Andersson, G.,
"Design aspects for wide-area monitoring and control systems,"
Proceedings of the IEEE, Volume 93, Issue 5, May 2005 .
© 2007. All rights reserved.
|
 
Other Articles on Voltage Stability:
"The In-Between Voltage State,"
by
R. Austria, December 2005.
"Living on the Ledge - Operating
Distribution Systems at Low Voltage,"
September, 2006.
R. Austria, "The Voltage Ledge," April 2007
"Application of DVRs in
Networks Subject to Reactive Deficiencies,"
March, 2007.
"Observability and Controllability in
Highly Compensated Systems ," September 2007
"Rising Out of the Trench: Insight from
the Voltage Response Curve," October 2007
|