Is Solar the Next Wind?
August 2006
Pterra Consulting
Continuing our series on integrating renewable energy into today's
power systems, we now turn our attention to solar energy. Solar is
another growing renewable resource for electric power. Total
installed capacity worldwide powered by either solar panels or solar
reflector installations is estimated at 10,000 MW as of 2005, with the
largest capacities in Japan, Germany and the United States. About
80% of this capacity is grid-connected.
There are numerous conversion technologies currently available or
under development. The primary ones used for bulk power
are:
-
photovoltaics
(PV)- use the photovoltaic effect of semiconductors to
generate electricity directly from sunlight. A variant,
concentrated photovoltaics, uses lenses to concentrate sunlight into
a smaller panel of high efficiency PV
- thermal - use solar heat to run a steam turbine or an
induction generator. For further discussion, we'll refer to
the steam turbine system by its commercial name - SEGS for
the solar energy genrating system developed by Solel, and to the
induction generator as SES for Stirling Energy Systems,
developer of that design.
The
largest existing or under construction PV installations are on the order
of 10-11 MW (Bavaria Solarpark in Germany, GE solar plant in
Serpa, Portugal). The largest thermal installations of SEGS are
located in the Mojave Desert in the United States where plants ranging
in size from 14-80 MW provide a net capacity of 345 MW.
Two installations of thermal solar using SES have recently been proposed
in Southern California with sizes of 500 and 300 MW.
With this type of growth and advancement, one wonder if solar is the next wind?
What is unique about solar fields?
Solar energy conversion
technologies have many similarities with wind power (see "The Renewables: Part 1 - Wind
Farms," Techblog of May 2006). Like wind, solar increases the
delivered electric energy by terrain and acreage. In the case of
solar, deserts are an ideal location. The hotter the better.
And like wind, to obtain power levels above 50 MW requires a farm or
park of many
individual collectors interlinked by power lines and cables. Ultimately, the lines connect to substations which step up the voltage
to transmission levels and interconnect with the power grid. Now,
the actual energy conversion from solar to electric energy is what makes
this resource unique.
-
With PV, solar panels convert the sun's rays into direct current
(DC). The DC is passed through inverters to obtain alternating
current (AC) than can be stepped to higher voltages and shipped over
long distances [See
Ref 1].
-
SEGS
design has been in operation since 1984 and involves a hot fluid
loop to collect thermal energy and drive a conventional steam
turbine [See
Ref
2].
- SES is more recent, although the technology for the Stirling
engine is nearly 200-years old. The system uses dishes to
concentrate sunlight onto a fluid loop. The same fluid
then operates an engine to produce electric power. The design
provides for silent, no-emission operation [See
Ref
3].
A summary of solar energy characteristics:
-
Output Predictability: The output from a solar
field depends primarily on the prevailing solar output. This would
be ideal support for day peaking systems, and a stark contrast to wind
power which peaks at night and can be still when the day is at its
hottest. Collectors take into account the
position of the sun over the course of the day and through the seasons.
Output is only available during daytime. This might be extended a
short extent into nighttime with the help of batteries or energy storage
systems. Solar
presents a planning challenge in how to account for the energy available
for this resource when looking ahead 2-5 years medium term or 5-10 years
long-term.
-
Variability:
Cloud cover and weather patterns add a second layer of complexity to
predicting delivered power. This presents an operating challenge to
integrate the solar output with the overall energy portfolio for
electric supply. More and more, storage energy options are seen as a means to provide operators greater
flexibility in meeting cyclical load demand.
-
Voltage Control. If inverters or induction generators are used, there is generally
limited reactive power control. For low voltage ride-through (LVRT) ,
inverters can be provisioned with battery energy systems (BES), rotating energy from
flywheels, super magnetic energy storage (SMES) or fast reactive sources
such as static var compensators (SVC). Special design induction generators can
be equipped to withstand the mandated LVRT capability, with additional
protection from voltage and frequency relays. A steam turbine
moving a generator with sufficiently capable excitation control will not
generally have a problem with respect to voltage control.
System Impact Concerns
The technical concerns with integrating solar fields are:
- Steady-state - the solar field must meet reliability
standards for thermal loading and voltage during normal operations and under credible
contingencies. The analysis may include any impacts on
thermally or voltage limited interfaces. Mitigation
may include transmission reinforcement, capacitor addition, remedial
action schemes and other transmission planning solutions.
- Fault levels - the solar field should demonstrate
mitigated impact on short circuit levels. Inverter technology
does not contribute significantly to fault levels. Thermal solar conversion with
wither steam or induction generators
introduce increases to the fault levels that have to be checked
against existing and planned withstand capacity.
-
Stability - the solar field must meet reliability standards
for acceptable levels of oscillations, damping, transient stability
and long-term stability when integrated with an existing grid.
The tests cover normal, emergency and and extreme contingencies with
varying levels of acceptable response. The plant will be
required to stay online during close-in normal faults and meet the
mandated LVRT capability.
- Switching - If mitigation includes switched capacitors, the size should not
exceed allowable delta-V at the load and transmission buses.
- Power Quality - The operations of inverters may introduce voltage flicker
and harmonic distortion into the system. The level should be
kept within acceptable criteria defined by standards.
Mitigation may include filters and static var devices.
- Subsynchronous Resonance - Inverters may introduce excitation currents that may
excite resonant frequencies in closeby steam generators. Torsional analysis may be needed to demonstrate potential
impacts from torsional stresses.
Modeling Issues
Solar
fields using PV or SES designs would electrically operate as distribution systems
with line voltage in the range of 4-69 kV for connections between
collector stations. For bulk power studies, the collectors can
themselves be aggregated into equivalent collectors in terms of how the
transmission grid would view them electrically.
The modeling challenge is to figure out the characteristics of the
various aggregates for each of the analytical tests - steady-state power
flow, short-circuit, switching, stability, etc.
Solar fields based on SEGS would appear as small to medium-sized steam
generators to the power grid. Steam generators are familiar ground
to most planners and analysts, and for the purposes of this discussion,
SEGS are excluded from the Modeling Issues coverage.
Power Flow Modeling
For power flow modeling, each collector aggregate is represented by the combined real power generation
of the individual inverters or induction generators.
Reactive power is modeled depending on the reactive control strategy,
the typical being application of static reactive compensation to bring
the net power factor to unity. The impact of energy storage would
be to provide some range in the reactive power in the steady-state.
Like wind farms, solar fields are also susceptible to voltage drop on certain
line out contingencies. Power flow solution
algorithms may diverge in these cases. Among techniques to confirm
that the issue is a physical rather than a numerical issue are:
- Adding a fictitious synchronous condenser
- Changing solution method - a full Newton solution that
recalculates the Jacobian every iteration would work best in this
case
- Changing the solution acceleration factor (in PSLF, the reactive
solution factor may also be changed)
- Changing location of the swing bus
Modeling for Short Circuit and Switching Analyses
If inverters are used, there is no contribution to short circuit.
Induction generators, on the other hand, would inject fault currents in
accordance with the magnitude of the machine reactance. This could
be either the subtransient (X"d) or transient (X'd) reactance.
Since the generator may represent an
aggregate, the reactance used would
be the same value if all the generators have the same characteristics on
a machine base which is the sum of the MVAs of the individual machines.
For switching analysis, a more detailed model is required.
Avoiding aggregation is the first consideration. The impedance of
overhead lines and cables, and transformers would need to be modeled
explicitly.
Modeling for Dynamic Simulation
First, let us deal with solar fields that use inverters. The
inverters have controls that may be able to adjust the real and reactive
power output of the solar farm depending on voltage and frequency at the
collector terminals. In addition, there may be additional
equipment, noted earlier, that may be included in the installation to
meet LVRT requirements, provided extended operating life or to condition
voltage. The aggregate response of the inverters
and additional equipment would need to be modeled specifically for each
design. (For further information on special model development, see "Developing My Dynamic
Model,"
by M. Gutierrez, Techblog of March, 2006.
On the other hand, for solar fields that use induction generators, the
model for dynamic simulation is based on an equivalent induction
generator which represents all the induction generators in a collector
bus. If all the generators are the same , then the electrical
characteristics of one unit can be used with an MVA base equal to the
sum of MVAs of the individual units. The controls of the solar
dishes may show some dependence on the voltage and frequency of the
collector terminals, and these would have to be included in a detailed
special model.
Since the PV and SES conversion technology for solar power results in an
asynchronous device (inverter or induction generator) conventional aspects of generator performance related to internal angle,
excitation voltage, and synchronism are not applicable. We
would have to infer the impact of the solar farm from the
rotor swing curves and damping simulations of neighboring synchronous machines.
Another indicator of solar farm dynamic performance would be the voltage
and frequency at the terminals, especially the LVRT capability.
Note that though it would be tempting to represent the solar field as a
standard induction machine, its inherent controls would shift response
away from this assumption.
Conclusions
Solar fields are a growing component of today's power systems.
Conversion technologies are evolving rapidly. Planners, operators
and designers would need to keep abreast of developments to anticipate
integration and operating issues for these new resources.
Specifically, new analytical methods and models may be required
to ensure that their specific response characteristics are captured
accurately for simulation and study.
The main challenge is whether we can be pro-active to the
changes that solar energy in its many forms of conversion technology and
design will most certainly bring to the table.
For questions, comments and further discussion, contact us at
mailto:info@pterra.us
References
- "Bavaria
Solarpark", Powerlight website
- "Solar Fields for Utility Power Plants,"
Solel website
- "What
is a Stirling Engine?" Stirling Energy Systems website.
- "The
Basics of Solar Power for Producing Electricity," Advanced
Energy Group website
© 2006. All rights reserved.
|