|

Steel Mills in the Neighborhood (Part 2 - in Your Backyard)
April 2006
The
steel industry is just giddy on new
and upgrades to steel mills. Google the subject and you'll find
--- the Minnesota Steel & Iron project in
Itasca County, MN, the upgrade of the Pacific Steel Casting mills
in
Berkeley, CA, and Brazilian steel company CSN's plans to build a
steel-rolling mill in Kentucky, among others, in recent news.
For whatever the reason, mill developers see an increased demand for their product
providing impetus for increased capacity. A key economic factor
for additional milling capacity is the availability of steady,
low-cost power supplies for their mills.
This bodes well for the power industry in at
least one respect --- mills represent a high load factor customer, not a
lot of MW installed required for the annual energy consumption.
However, they do pose new challenges to maintaining reliability and
power quality.
Technology
Electric aspects of mill technology have advanced
significantly in a number of key areas, including:
improvements rolling processes, faster reactive controls on static var
compensators [4], being able to interconnect to weak grid nodes using
DC arcing [6]. Economies of scale applied to mill design have resulted
in larger mill sizes. Mills have become quite
good citizens on the power grid, cooperating with operators,
controlling, if not reducing, their power quality impact and operating
efficiently and reliably.
Technical due diligence requires that we address
the technical concerns. The
failures at Comanche station (power spikes
from a neighboring mill) [8] and at Port Washington (torsional
interactions with a steel plant) [7] were not too long ago to be
forgotten. New torsional
relays offer protection against recurrence. But how reliable
and effective will these devices be? Also, we have yet to see
standard generator protection schemes cover
flicker and harmonics.
To clarify these issues seemed like a good idea
for a second article on this subject. For the first Techblog on
steel mills, please click on this link.
More Quality Issues
Modern steel mills comprise of two arc
furnaces of 100 MW or more each, a rolling mill of about 175 MW, a
static var compensator (SVC) and harmonic filters [1]. The demand MWs
vary in accordance with perhaps up to 5 different load cycles that can
lead to an average, cyclic load impact of 150 MW and extreme load
impacts of 200 MW. The cyclic load introduces flicker and each
impact load generates harmonic currents. In addition, the SVC
controls introduce both flicker and harmonics, and capacitors modify
frequency response.
To control flicker, mills are typically located where the
fault levels are high (or where the system is relatively stiff).
This means locating close to a power plant or to a strong nexus of high
voltage transmission lines. Generators, due to their low impedance
to ground, act as a harmonic sponge, absorbing harmonic currents from
the steel mill plant. So having them close to a mill is
beneficial, since they would generally reduce total harmonic
distortion in the system. However, an undesired effect of this
proximity is the heating that the harmonic currents cause in generators.
An even more ominous impact of proximity is the potential excitation of
turbine shaft resonant modes that can lead to torsional stress and shaft failure.
Recently, solutions have been developed to allow
interconnection even at weak nodes of the grid. If effective, this
may lead to siting of mills away from generators, leaving the power
quality mitigation on the hands of SVCs (with fast controls) and
well-designed harmonic filters, and avoiding the potentially hazardous
side effects on the generators.
Case Study
In January 2004, the PSCo Comanche 2 station experienced a
catastrophic failure. The initial indication was that the bindings
at the end of the generator rotor that support the end turns of the
copper windings broke free and hit the stator. This type of
failure is normally associated to corrosion. However, in this
particular case, there was steel mill close by ...
The
steel mill included two DC arc furnaces for which voltage flicker
control was implemented through a static var compensator (SVC).
The SVC produced a variety of exciting frequencies from the combined
which varied as a function of the changing short circuit ratio (SCR) at
the point of common coupling with the network. The SCR changes as
the external load changes. The SVC operation itself varied as the
steel mill's load cycle, resulting in a cyclically varying set of
excitation frequencies.
In the prior prior to the failure, one of the exciting frequencies
coincided with a resonant frequency in the Comanche 2's shaft.
Somehow, this did not cause the same issue with Unit 1, and the
conjecture is that modifications made to Unit 2, also changed its
resonant frequencies. The repeated excitation in Unit 2 caused
torsional stress that eventually led to the failure.
Mitigation measures applied to Unit 1 included modification of the
SVC controls to change the exciting currents, modification to the shaft
to eliminate resonance close to frequencies developed by the steel mill,
and the continuous monitoring of shaft vibrations.
Treatment options
Treating some of the issues one at a time then:
-
Flicker. Comes from the mill operations
and SVC [2]. Tend to be worst at light load, when fault levels are
lowest. Standards such as IEEE 519 provide basis for
acceptance criteria. Impacts primarily customers with
lamps, noting that the tolerance level from incandescent and
fluorescent
lamps may differ. Is mitigated by increasing the
SVC range and/or locating close to a large power plant, or using DC
arcing. May
also be mitigated operationally by reducing power level of the mill during certain
system conditions or shutting down the mill altogether.
-
Harmonics. Comes from the mill
operations, SVC and capacitor banks. Analyzed with a frequency
scan at various operating configurations [5]. Typical levels by harmonic
number for various components of the mill may be applied to estimate
the currents introduced into the grid. When the mill is
already in service, field measurements would refine the harmonic
contributions. Tend to be worst at peak load when the
harmonic modulation is applied to higher current amplitudes, and
when the harmonic is close to a resonant frequency. Impacts
primarily equipment that are sensitive to voltage spikes --- rotating
equipment
such as generators. Can be mitigated by harmonic filters or
design/operation of capacitors and SVC to avoid resonance at
critical harmonic frequencies.
-
Torsional interaction. Only an issue
when there is a generator nearby whose shaft may have resonant
frequencies that can be excited by a mill's mix of harmonic and
non-fundamental currents. The effect is similar to what may be
found when series capacitors excite subsynchronous resonance.
However, mill operations have a cyclical characteristic that may
accumulate a relative small level of excitation to a stress failure.
Mitigated by designing and operating the system carefully to avoid
matching a shaft resonant frequency. Torsional relays may
provide protection. These are relatively new.
The whole ball of wax ...
Note that solutions to resolve flicker lead to
other issues --- locating close to a generator for the higher short
circuit ratio exposes that generator to harmonic heating and torsional
stresses, while increasing the SVC capacity to introduce stiffness can
lead to increases in harmonic currents and torsional interactions.
Solutions that may work for the initial operations of the mill may no
longer do so as the surrounding system evolves over time. This is
especially a concern for resonance and torsional stresses.
The full solution tends to be an intricately
planned, designed and operated marriage of mill and power system that
addresses the whole range of quality and reliability issues. The
careful engineering is required because some of the mitigation have side
effects that require additional forms of mitigation.
References:
-
The
impact of large steel mill loads on power generating units, Solanics, P. Kozminski, K. Bajpai, M. Esztergalyos, J. Fennell, E.
Gardell, J. Mozina, C. Patel, S. Pierce, A. Skendzic, V. Waudby, P.
Williams, J., Power Delivery, IEEE Transactions, Jan 2000, Volume:
15, Issue: 1, pages 24-30.
-
An EMTP study of flicker generation and transmission in power
systems due to the operation of an AC electric arc furnace,
Ramos, B.N.; Parga, J.L.deC.; Harmonics and Quality of Power, 2000.
Proceedings. Ninth International Conference on Volume 3, 1-4 Oct.
2000.
-
Updating a steel mill power system to improve reliability and
decrease energy costs, Albaugh, J.R.; Kornblit, M.J.; Industry
Applications, IEEE Transactions on, Volume 30, Issue 5, Sept.-Oct.
1994.
-
Static Var compensator upgrade in a steel mill, Depommier, B.;
Stanley, J.; Power Engineering Society General Meeting, 2003, IEEE,
Volume 1, 13-17 July 2003.
-
Harmonic and transient overvoltage analyses in arc furnace power
systems, Mendis, S.R.; Gonzales, D.A.; Industrial and Commercial
Power Systems Technical Conference, 1990, Conference Record. Papers
Presented at the 1990 Annual Meeting, 30 April-3 May 1990.
-
Comparison of some active devices for the compensation of DC arc
furnaces, Carpinelli, G.; Russo, A.; Power Tech Conference
Proceedings, 2003 IEEE Bologna, Volume 2, 23-26 June 2003.
-
Retaining Ring Cracking at Wisconsin Electric Power Company's Port
Washington Unit 1 -- Root Cause Analysis, EPRI Report, June
2002.
-
Retaining Ring Cracking at Comanche Unit 2 -- Root Cause Analysis,
EPRI Report, July 1996.
For questions, comments and further discussion, contact us at
mailto:info@pterra.us
© 2006. All rights reserved.
|
 
Read Part 1 of this Article
Other Articles
|