|

Steel Mill in the Neighborhood
January 2006
As
a type of electrical load, steel mills are the equivalent of
jackhammers early in the morning. If you're not prepared for them,
they can cause headaches. Steel mills, with arc furnaces, have a
randomly varying demand that can swing as much as 200 MW for a
300 MW steel plant every 30-90 minutes or so. The effects of this load
change may be noticed in lights, PC's, and TV's. When a mill's furnace comes on, the voltage dips and
rises when it is switched off. Voltage and the frequency will
change and result in a change of light intensity. In addition, the
arcs in each furnace of the mill can result in an imbalanced load that
is loaded with harmonics that varies cycle to cycle creating what one
may call "dirty" power. This load connected to the grid can affect other
customers connected to the grid.
In the grid itself, there is need to provide
adequate capacity to supply the range of demand of the steel mill.
A 300 MW mill will require at least two 230 kV circuits, and any
upgrades to the network to bring the 300 MW to the load point, including
voltage support. Equipment need to be designed to withstand the
maximum switching surge. The network needs to have sufficient
damping of oscillations from each change in demand from the mill.
Frequency dip during load pickup may reach below the threshold at which
under-frequency load shedding relays are set, and trigger nuisance
trips.
To the electrical emanations from the mill, a
large turbine-generator looks just like another load. Thus, mills
introduce harmonics and negative sequence currents that can cause
rotor
heating. Moreover, mills using cyclo-converter drives may produce
sub-synchronous resonance that can excite turbine-generator torsional
vibrations. On the other hand, steel mills feed on the bountiful and
agile supply of reactive power from the generator. Smaller turbines, such as
wind mills, are also susceptible to the harmonics coming from steel
mills. Both frequency and voltage dips must be within tolerance of
the wind farm protection and low-voltage ride-through capability.
All this makes for a sometimes
unfriendly
neighbor on the grid. The magnitude and breadth of the impact from
a steel mill varies by grid and, for certain
specific effects, by location of the mill in the grid. There are
known medicines or countermeasures for specific types of impacts.
But there is no single cure-all. Before one
can prescribe the type and strength of countermeasures, it is important
to conduct a detailed analysis, or as the doctor would say, "We have to
do some tests."
Types of Tests
The battery of tests to evaluate a steel mill's impact can include:
system simulations involving power flows, contingency analysis, short
circuit, transient switching, stability and extended dynamics, torsional
analysis, harmonic measurements and voltage flicker analysis. The
specific regimen of tests depend on whether the mill exists or is the
design stage, the size of the mill loads and it's relative location on
the grid.
The system tests are generally
treated as impact studies, but for thoroughness, we recommend a planning
approach wherein not just the initial year of operation is tested, but
rather over time, in conjunction with the development of the grid. In
many cases, the impacts, especially on power quality are localized and
once the prescription for controlling the PQ impacts are made
measurements are needed to ensure that the impacts are controlled within
acceptable criteria.
The system response performance is tested against the system
reliability, voltage flicker, harmonic and frequency criteria which would include acceptable response to probable
disturbances such as first contingencies, as well as extreme
contingencies. Fundamental frequency impacts can be determined
from long-term dynamic simulations or thru approximation.
For instance, the during the first half second after the load swing,
you can apply the following rule of thumb derived from the energy
balance: f = SQRT (1. - dP * 0.5/ Ke). For a dP = +/- 200 MW
and neighboring plants of 2000 MW-sec of steady state kinetic
energy, then the frequency changes are in the order of +/-1.5 Hz
for a 60 Hz system. Subsynchronous frequency impacts require a
torsional analysis that evaluates the response of turbine generator
mass-damping systems to SSR from mill operations. The test is
to ensure that there is adequate damping in the mechanical system to
contain any subsynchronous excitation.
Power quality is measured against several industry
standards, including flicker standard IEC-41000 and
IEEE 519.
Once the impacts of the mill are known, then we can move on to
identifying solutions.
Types of Countermeasures
The proximity of equipment, such as a generator, to the mill make
them vulnerable to harmonics developed during the steel-making
processes. To contain the harmonics would require a carefully designed
harmonic filter within the steel mill.
If the mill fails the flicker and/or voltage dip standards, a typical
solution is to implement a static var device (SVD). The SVD should be
sized to fully compensate for the reactive demand of the electric arc
furnaces,
ladle furnaces, rolling mill and other loads in the mill, including any
additional reactive power needed to help control the voltage drop caused
by MW and Mvar load changes. The control of the SVD should be an open-loop control between
the SVD and furnaces to provide faster response to load changes. A
slower closed loop control is often employed for power factor or var
demand control. A substantial power plant close to the mill could
provide sufficient voltage "stiffness" that the SVD may not be required
for flicker control. However if a rolling mill is present, harmonic
filters may be required due to the high percentage of drives on variable
speed control.
Switching of large loads could cause unacceptable frequency
excursions for relatively small grids, grids with low overall inertia or
with slow or no frequency control. To provide the necessary frequency
control, a lower ramp rate on the load may be one option. Other frequency
control options may require changing turbine governor settings, or enabling or
changing out controllers in generators.
Detectors and planned automatic response systems may sometimes offer
a cheap prescription to a mill system impact. For example relays
to detect unhealthy torsional impacts may trip a generator from further
harm. Harmonic monitors may be set to trip the mill when
distortions exceed acceptable levels.
Any other system reliability impact are addressed in the normal
fashion of system planning studies, through new transmission, upgrades,
voltage support, and the like.
Conclusion
Despite the potential headaches, many steel mills are able to
integrate well with the neighborhoods they share the grid with.
Through careful application of specific countermeasures, the impacts can
be contained. It's always a good idea to do some pre-operational
testing prior to bringing one online.
References:
- "The
impact of large steel mill loads on power generating units,"
Solanics, P. Kozminski, K. Bajpai, M. Esztergalyos, J. Fennell, E.
Gardell, J. Mozina, C. Patel, S. Pierce, A. Skendzic, V. Waudby, P.
Williams, J., Power Delivery, IEEE Transactions, Jan 2000, Volume:
15, Issue: 1, pages 24-30.
- "Dynamics
of a large induction motor load system," Undrill, J. Renno, A.
Drobnjak, G., Power Engineering Society General Meeting, 13-17 July
2003, Volume 3, page 1403.
Notes:
- Although the above has focused on a large
arc-furnace mill, a rolling mill can have the same effect. However, the
change in the rolling mill load MW's are generally not as great as an
arc-furnace.
For questions, comments and further discussion, contact us at
mailto:info@pterra.us
© 2006. All rights reserved.
|
 
Read Part 2 of this Article
Other Articles
|